S-800W series normal single switchingpower supply
Features:
·AC input voltage range selected by switch
·Small volume,low weight,high efficiency
·Protections:short circuit/over load/over voltage/overtemp
·Built-in cooling DC fan
·Can be used parallel connection
·LED indicator for power on
·100% full load burn-in test
·2 Years warranty
Model | S-800-12 | S-800-15 | S-800-24 | S-800-27 | S-800-36 | S-800-48 | |
output | DC voltage | 12V | 15V | 24V | 27V | 36V | 48V |
Voltage tolerance | ±1% | ±1% | ±1% | ±1% | ±1% | ±1% | |
Rated current | 66A | 53A | 33A | 29.5A | 22A | 16.5A | |
Current range | 0~66A | 0~53A | 0~33A | 0~29.5A | 0~22A | 0~16.5A | |
Rated power | 792W | 795W | 792W | 796W | 792W | 792W | |
Ripple&noise | 200mvp-p | 200mvp-p | 240mvp-p | 240mvp-p | 300mvp-p | 300mvp-p | |
DCvoltage ADJ.range | -9%~+10% | ±10% | ±10% | ±10% | ±10% | ±10% | |
input | Voltage range | 90~132VAC/180~264VAC(selected by switch),255~373VDC | |||||
frequency | 47~63HZ | ||||||
AC current | 16A/115VAC,8A/230VAC | ||||||
efficiency | 80% | 81% | 82% | 82% | 83% | 84% | |
Inrush current | Cold start current25A/115VAC,50A/230VAC | ||||||
Leakage current | < 3.5mA/240VAC | ||||||
protection | overload | Rated output power115%~135% start over load protection | |||||
protection type:cutoff output,recovery after restart power | |||||||
Over voltage | 15.6~17.8V | 18.6~20.8V | 30.6~33.2V | 33.2~35.6V | 42.6~44.2V | 54.8~56.6V | |
protection type:cutoff output,recovery after restart power | |||||||
Over temperature | detect on heatsink of power transistor≥85℃start over temperature protection | ||||||
Protection mode:cutoff output,auto-recovery after temperature become normal | |||||||
environment | Working temp,humidity | -10℃~+60℃,20%~90%RH | |||||
Storagetemp,humidity | -20℃~+85℃,10%~95%RH non-condensing | ||||||
Withstand vibration | 10~500HZ,2G10min/1cycle,period for 60 minutes,each axes | ||||||
safety | Withstand voltage | I/P-O/P:1.5KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | |||||
Isolation resistance | I/P-O/P,I/P-FG,O/P-FG:100Mohms/500VDC | ||||||
Fitstandard | Safety standard | Compliance to UL1012 | |||||
EMC standard | Compliance to EN55022,CLASSA | ||||||
others | Dimension | 247*127*63.5mm(L*W*H) | |||||
Weight/packing | 2.1kg/9pcs/20kg/0.029m³/1.04CUFT | ||||||
note | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and25℃of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. |